UPS users manual
(Please read the manual carefully before using)
Qinhuangdao Xinchi Photoelectricity Technology Co., Ltd
Operation Panel
Uninterruptible Power Supply
ModelXC-BD-UPS0001
Input: AC100V-50Hz/60Hz-1.5Kw
Output: AC100V-50Hz-3Kw
Battery Nominal Voltage51.8V
Battery Capacity: 4KWh
Protection Grade: IP32
2. Technique specification
Item |
Technology standard |
AC power supply input port |
1 units |
AC input voltage |
AC110V 15V |
Max. Input current |
AC15A |
| |
AC power supply output port |
2 units |
Inverter output voltage |
AC110V 5V |
Inverter output power |
3KVA |
AC output switch |
1 unit |
Limited current of AC output switch |
AC10A |
| |
Inner battery cell model |
XC-CSM1865130 |
Battery pack solution |
8P14S |
Battery pack Nominal Voltage |
DC51.2V |
Battery pack working voltage range |
DC32V-58.4V |
Battery pack max. storage energy |
4.1KW.H |
Battery pack charge current |
15A |
Max. Charge voltage |
DC58.4V |
Battery pack main control air switch |
1units |
Limited current of Battery pack main control air switch |
15A |
| |
Solar input port |
1 unit(SB50) |
Remark: when battery pack is full, automatically cut off the solar input port | |
Solar Charge current |
10A |
Solar cell power |
800W |
Affix 2: Inversion System Parameters
Item |
Technical Index |
Nominal Output Capacity |
3KVA |
Overvoltage Protection for Inverter Input |
68V DC |
Overvoltage Recover for Inverter Input |
66V DC |
Floating Current |
0.42A |
Output Waveform |
Pure Sine Wave |
Display Mode |
LCD Screen |
Nominal Output Voltage |
110V AC |
Waveform Distortion Rate |
4% |
Output Frequency |
60Hz0.5Hz |
Dynamic Response |
5% |
Overload Ability |
120%(1 minute), 150%(10 seconds) |
Inversion Efficiency |
Max 90% |
Protective Function |
Inverter output overvoltage protection, Output overload protection, Output short-circuit protection, overheat protection |
Working Temperature |
-20~50C |
Working Altitude |
4000m |
Working Humidity |
0~90%, no moisture condensation |
Affix 3: Charging System Parameters
Item |
Technical Index |
Input Voltage Range |
AC110V |
Output Voltage |
58.8V |
Output current |
15A |
Overload Adjustment Rate |
Output5%~100% Full load |
Efficiency |
Output Full Load |
Dynamic Response |
20%~100% overload |
Input protection (Output 50% overload) |
Overvoltage protection, stop output |
|
Normal power grid, recover output |
Output overvoltage protection |
Overvoltage protection, stop output |
Working state
When open the invert switchthe equipment outputs 100Vthe socket and terminals N L back of the equipment could output 100V.
The display screen of inverter will show two voltage values. The first one is battery voltage, the second one is output voltage(100V normally)
Battery capacity indicator
Battery capacity indicator will light. Please charge in time when the last one indicator light. It completely is not necessary that do the charge until the batteries discharge to zero.
Charging state
Make the 100V alternating current access the connection ports AC IN back of battery, then open the charge switch. At this time, the charge display screen will display. And the switch near screen will change over the current display and the voltage display.
The current is 0A, voltage is 58~58.8V, which means that the charging has reach fullat this time all the indicators will light, in the situation of invert open
Based on characters of this battery, the charging at any time will not injure battery. So, please do charge in time if you can.
It will take 5 hours from full discharging to full charging.
The time of charging is depends on the using of the home equipment.. 2kwh equipment as Example,it can supply 2hours.
Using Guide
u Environment condition
2 Charge temperature 045
2 Discharge temperature -2055
2 Storage temperature -2035
2 Altitude no more than 2000m
2 Average relative humidity no more than 65%25棩
2 Away from application in seriously tremble
2 No corrosive gas in the surrounding medium
Transportation and storage
u Transportation
In transportation, the battery should be gently moved in the delivery period, throw, roll and pressure are forbidden to the battery.
u Storage
In the process of storage, the loaded retention should be less than 50% and have a charge every six months. Optimum storage temperature is 530 in dry, clean and ventilation room.
Storage battery should avoid direct sunshine and placed more than 2m away from heat source.
Battery shouldnt be inversed, and avoid mechanical impact or stress.
Attention items
u Far away from heat, water and fire.
u Dont disassemble, reassemble, dissection battery or battery group.
u No disassemble and refit of the charger.
u Dont reverse the battery positive electrode and negative electrode.
u Dont short circuit the battery positive electrode and negative electrode.
u Dont put the charger and battery in water or wet place.
u Dont cast charger and battery randomly.
u Dont puncture, scar the battery.
u Dont use the battery in other fields.
u Using special charger to charge.
u Carefully read the specification before using the battery.
u Every three months the battery should be charged two hours.
NO WARRANTY IF USED FOR UTMOST TESTING